Formate coolants Nordway-FORM

Used for various types of the cooling equipment. Depending on concentration Nordway-FORM cooling is possible up to -60C. The product unites good antifreezing characteristics with excellent anticorrosive properties, this combination and a high level of safety opens wide opportunities for its use at the enterprises of the food-processing industry. Nordway-FORM is not toxic, almost without a smell a liquid containing special inhibitors of corrosion and stabilizers. Its corrosion protection covers all the basic metals used in cooling technologies: steel, corrosion-proof steel alloys, pig-iron, a brass, copper, aluminium, etc.  

1. Nordway-FORM 60
Developed: for working in temperature modes from +40C up to -60C It has good thermo physical properties, low corrosion activity, low danger (4 class of danger).  
Recommended: for application in refrigerating systems with working temperature up to -60C and as a concentrate for other consumers.  

Comparative properties Nordway-FORM 60
Name
Temperature
Density
The Specific thermal capacity
Heat conductivity
Kinematic viscosity
 
Minimally recommended working temperature -60oC
[C0]
[gr/sm3]
[kJ*103/m3*K]
[watt/m*K]
[mm2/s]
40
1,375
0,651
1,70
2,34
30
1,380
0,647
1,80
2,48
20
1,385
0,645
2,50
3,46
10
1,389
0,64
3,40
4,72
0
1,394
0,635
5,30
7,39
-10
1,399
0,630
8,80
12,31
-20
1,404
0,626
17,50
24,57
-30
1,410
0,625
31,00
43,71
-35
1,415
0,62
35,00
49,53
-40
1,420
0,615
44,00
62,48
-50
1,425
0,61
76,00
108,3

1. Nordway-FORM 50
Developed: for working in temperature modes from +40C up to -50C It has good thermo physical properties, low corrosion activity, low danger (4 class of danger).  
Recommended: for application in refrigerating systems with working temperature up to -50C and as a concentrate for other consumers.

Comparative properties Nordway-FORM 50
Name
Temperature
Density
The Specific thermal capacity
Heat conductivity
Kinematic viscosity
Minimally recommended working temperature -50oC
[C0]
[gr/sm3]
[kJ*103/m3*K]
[watt/m*K]
[mm2/s]
40
1,345
0,632
1,35
1,82
30
1,350
0,630
1,88
2,54
20
1,355
0,628
2,17
2,94
10
1,359
0,627
2,50
3,40
0
1,370
0,625
3,00
4,11
-10
1,374
0,623
4,50
6,18
-20
1,378
0,621
6,70
9,23
-30
1,382
0,620
13,00
17,97
-40
1,385
0,619
18,00
24,93
-50
1,387
0,618
23,50
32,59

1. Nordway-FORM 40
Developed: for working in temperature modes from +40C up to -35C It has good thermo physical properties, low corrosion activity, low danger (4 class of danger).  
Recommended: for application in refrigerating systems with working temperature up to -35C and as a concentrate for other consumers.

Comparative properties Nordway-FORM 40
Name
Temperature
Density
The Specific thermal capacity
Heat conductivity
Kinematic viscosity
Minimally recommended working temperature -35oC
[C0]
[gr/sm3]
[kJ*103/m3*K]
[watt/m*K]
[mm2/s]
40
1,317
0,615
1,35
1,78
30
1,321
0,620
1,75
2,31
20
1,325
0,621
1,87
2,48
10
1,323
0,623
2,97
3,93
0
1,333
0,624
3,50
4,67
-10
1,339
0,630
5,60
7,50
-20
1,344
0,640
7,70
10,35
-30
1,350
0,650
11,5
15,53

 

1. Nordway-FORM 30
Developed: for working in temperature modes from +40C up to -25C It has good thermo physical properties, low corrosion activity, low danger (4 class of danger).  
Recommended: for application in refrigerating systems with working temperature up to -25C and as a concentrate for other consumers.

Comparative properties Nordway-FORM 50
Name
Temperature
Density
The Specific thermal capacity
Heat conductivity
Kinematic viscosity
  Minimally recommended working temperature -25oC
[C0]
[gr/sm3]
[kJ*103/m3*K]
[watt/m*K]
[mm2/s]
40
1,244
0,645
1,31
1,63
30
1,250
0,650
1,46
1,83
20
1,255
0,653
1,70
2,13
10
1,259
0,655
2,21
2,78
0
1,264
0,658
3,07
3,88
-10
1,269
0,659
3,72
4,72
-20
1,274
0 .700
4,00
5,10
   
RCP Nordix JSC